Insulated Conductor Rail
NSP-H unipole insulated conductor rail system is a modern mobile power supply system. The material of conductor rail can be copper and aluminum. The aluminum conductor is mounted with a stainless strip to be long service life. Any numbers of poles of conductor rail can be installed vertically or horizontally, no matter on straight or curved system. This type of conductor rail also can be used indoor and outdoor.


Technical Data
Workshop 5S management
NSP-H unipole insulated conductor rail system is a modern mobile power supply system. The material of conductor rail can be copper and aluminum. The aluminum conductor is mounted with a stainless strip to be long service life. Any numbers of poles of conductor rail can be installed vertically or horizontally, no matter on straight or curved system. This type of conductor rail also can be used indoor and outdoor.


Technical Data
Unipole Conductor Rail system NSP-H Series | |||||
Conductor rail | Aluminium | Copper | |||
Type | H19 | H24 | H32 | H24 | H32 |
Nominal current at 100% DC and 35°C[A] | 150 | 250 - 300 | 320 - 1250 | 500 - 800 | 800 - 1600 |
D.C.resistance at 35°C [Ω/km] | 0.376 | 0.2030.187 | 0.1530.046 | 0.1160.067 | 0.0670.039 |
Impendance at 35°C [Ω/km] | 0.376 | 0.2090.195 | 0.1550.048 | 0.1180.069 | 0.0690.04 |
Support spacing [m] | 1.8 | 1.5 | 1.8 | 1.5 | 1.8 |
Rail length [m] | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 |
Housing length [m] | 3.88/5.88 | 3.88/5.88 | 3.83/5.83 | 3.88/5.88 | 3.83/5.83 |
Max.voltage [V] | 660V | Dielectric strength[KV/mm] | 30-40 | ||
Travelling speed | ≤ 600 m/min | Standard | GB7251.2-2006 | ||
Expansion joint | only required when total length ≥ 200m | ||||
Flame retardant | Class B1-no flaming particles,self-extinguishing | ||||
Permissible ambient temperature | Standard insulation -20C- +70C High temperature insulation -10C- +115C |
Type | Conductor Rail | Cross section (mm2) | Nominal current (A) | Leakage-distance (mm) | Resistance (Ω/km) | Weight (kg/m) |
NSP-H24-160/250 | Aluminium | 160 | 250 | 45 or 80 | 0.203 | 0.63 |
NSP-H24-180/300 | Aluminium | 180 | 300 | 45 or 80 | 0.187 | 0.71 |
Type | Conductor Rail | Cross section (mm2) | Nominal current (A) | Leakage-distance (mm) | Resistance (Ω/km) | Weight (kg/m) |
NSP-H32-230/320 | Aluminium | 230 | 320 | 80 | 0.153 | 0.96 |
NSP-H32-285/500 | Aluminium | 285 | 500 | 80 | 0.116 | 1.13 |
NSP-H32-360/630 | Aluminium | 360 | 630 | 80 | 0.087 | 1.38 |
NSP-H32-420/800 | Aluminium | 450 | 800 | 80 | 0.067 | 1.5 |
NSP-H32-550/1000 | Aluminium | 550 | 1000 | 80 | 0.058 | 1.83 |
NSP-H32-600/1250 | Aluminium | 600 | 1250 | 80 | 0.046 | 2.01 |